This is the name in FM standard, also known
as the direct injection variable pump output proportioner in China. The water
side and the foam side are respectively provided with a flow meter, the flow
meter measurement results are input to the PLC for processing, and then through
the relevant valve for pressure and flow regulation, so as to achieve accurate proportioning
rate. This kind of proportioner is basically not used in China, but it can
still be applied in mobile system, such as fire engines. However, the flow
range of this proportioner is limited by the measurement range of the flow
meter.
This proportioner is suitable for all kinds
of foam agents if the flow meter is correctly selected.